Recommended values of Static Capacitor in KVAR for power factor improvements | ||
A.Induction Motors(LT) | ||
Sl.No | Total Motor Rating (HP) | KVAR rating of capacitors insisted |
1 | Upto 3 | 1 |
2 | Above 3 upto 5 | 2 |
3 | Above 5 upto 7.5 | 3 |
4 | Above 7.5 upto 10 | 4 |
5 | Above 10 upto 15 | 5 |
6 | Above 15 upto 20 | 6 |
7 | Above 20 upto 25 | 7.5 |
8 | Above 25 upto 30 | 10 |
9 | Above 30 upto 40 | 12 |
10 | Above 40 upto 50 | 14 |
11 | Above 50 upto 60 | 18 |
12 | Above 60 upto 80 | 22 |
13 | Above 80 upto 100 | 25 |
14 | Above 100 upto 130 | 35 |
1 HP-746W | ||
B.Welding Transformers(LT) | ||
Sl.No | Rating of welding transformers in KVA | KVAR rating of capacitors insisted |
1 | 1 | 1 |
2 | 2 | 2 |
3 | 3 | 2 |
4 | 4 | 3 |
5 | 5 | 4 |
6 | 6 | 4 |
7 | 7 | 5 |
8 | 8 | 6 |
9 | 9 | 7.5 |
10 | 10 | 7.5 |
11 | 11 | 8 |
12 | 12 | 9 |
13 | 13 | 10 |
14 | 14 | 10 |
15 | 15 | 11 |
16 | 16 | 12 |
17 | 17 | 13 |
18 | 18 | 13 |
19 | 19 | 14 |
20 | 20 | 15 |
21 | Above 20 upto 22 | 16 |
22 | Above 22 upto 24 | 17.5 |
23 | Above 24 upto 26 | 18 |
24 | Above 26 upto 28 | 20 |
25 | Above 28 upto 30 | 21 |
26 | Above 30 upto 35 | 24 |
27 | Above 35 upto 40 | 27.5 |
28 | Above 40 upto 45 | 32.5 |
29 | Above 45 upto 50 | 35 |